SPECIFICATIONS
Supply Voltage:
D40-120V (Min. 102V: Max. 132V) 50/60 Hz.D41-230V (Min. 196V: Max. 253V) 50/60 Hz.
Power Consumption (Operating):
20 VA.
Maximum Simultaneous Connected Load:
2000 VA.
Ambient limits:
Control-Amplifier140º F (60º C)- 40º F (-40º C)
UV1A-UV2-UV8A-UV90 Scanner 200º F (93º C)- 40º F (-40º C)
45UV5 Scanner 200º F (93º C)- 40º F (-40º C)
48PT2 Scanner140º F (60º C)- 40º F (-40º C)
69ND1 Flame Rod (Tip 2460º F)1500º F (816º C)- 40º F (-40º C)
APPROVALS
70D41 only: TUV (Germany)70D40 only:Underwriters Laboratories Inc. Recognized: Guide MCCZ2, File MP 1537Factory Mutual System ApprovedNew York Board of Standards and Appeals 743-68-SA
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar deviceswhose inrush current is approximately the same as their running current.VA pilot duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total oper-ating load does not exceed the published rating and whose total inrush current does not exceed 10times the rating.Running and locked rotor ratings are intended for motors. VA and VA (pilot duty) loads may beadded to a motor load provided the total load does not exceed the published rating.
Supply Voltage:
D40-120V (Min. 102V: Max. 132V) 50/60 Hz.D41-230V (Min. 196V: Max. 253V) 50/60 Hz.
Power Consumption (Operating):
20 VA.
Maximum Simultaneous Connected Load:
2000 VA.
Ambient limits:
Control-Amplifier140º F (60º C)- 40º F (-40º C)
UV1A-UV2-UV8A-UV90 Scanner 200º F (93º C)- 40º F (-40º C)
45UV5 Scanner 200º F (93º C)- 40º F (-40º C)
48PT2 Scanner140º F (60º C)- 40º F (-40º C)
69ND1 Flame Rod (Tip 2460º F)1500º F (816º C)- 40º F (-40º C)
APPROVALS
70D41 only: TUV (Germany)70D40 only:Underwriters Laboratories Inc. Recognized: Guide MCCZ2, File MP 1537Factory Mutual System ApprovedNew York Board of Standards and Appeals 743-68-SA
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar deviceswhose inrush current is approximately the same as their running current.VA pilot duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total oper-ating load does not exceed the published rating and whose total inrush current does not exceed 10times the rating.Running and locked rotor ratings are intended for motors. VA and VA (pilot duty) loads may beadded to a motor load provided the total load does not exceed the published rating.