PRODUCT SPECIFICATIONS
Supply Voltage:
MBCE-110UV - 110 VAC (+20%, -15%), 50/60 Hz (@ 0.02 Amp consumption)
MBCE-230UV - 230 VAC (+10%, -15%), 50/60 Hz (@ 0.01 Amp consumption)
Flame Relay Output:
SPDT 1 Amp Resistive @ 110VAC, 1 Amp @ 30VDC
SPDT 1 Amp Resistive @ 230VAC, 1 Amp @ 30VDC
Flame Failure Response Time:
1 or 3 seconds-depending on part number (-1, -3) for CE
1, 2, 3, or 4 seconds-depending on part number (-1, -2, -3, -4) for UL
Operating Temperature:
- 40° F to 150° F (- 40° C to 65° C)
Storage Temperature:
- 58° F to 185° F (- 50° C to 85° C)
Humidity:
85% RH (max), non-condensing.
Agency Approvals:
MBCE-110UVULMBCE-230UV CE / EN298:2012
Shipping Weight:
1 lb (.5 Kg)
UV Scanner:
S1 = Terminal 4
S2 = Terminal 8
UV tube excitation Terminals 4 and 8, +300 VDC (max)
IP-Rating:
IP-20
Test Jacks:
Standby/No flame4mA
Flame signal (Min)5.5mA
Flame signal (Max)20mA
Supply Voltage:
MBCE-110UV - 110 VAC (+20%, -15%), 50/60 Hz (@ 0.02 Amp consumption)
MBCE-230UV - 230 VAC (+10%, -15%), 50/60 Hz (@ 0.01 Amp consumption)
Flame Relay Output:
SPDT 1 Amp Resistive @ 110VAC, 1 Amp @ 30VDC
SPDT 1 Amp Resistive @ 230VAC, 1 Amp @ 30VDC
Flame Failure Response Time:
1 or 3 seconds-depending on part number (-1, -3) for CE
1, 2, 3, or 4 seconds-depending on part number (-1, -2, -3, -4) for UL
Operating Temperature:
- 40° F to 150° F (- 40° C to 65° C)
Storage Temperature:
- 58° F to 185° F (- 50° C to 85° C)
Humidity:
85% RH (max), non-condensing.
Agency Approvals:
MBCE-110UVULMBCE-230UV CE / EN298:2012
Shipping Weight:
1 lb (.5 Kg)
UV Scanner:
S1 = Terminal 4
S2 = Terminal 8
UV tube excitation Terminals 4 and 8, +300 VDC (max)
IP-Rating:
IP-20
Test Jacks:
Standby/No flame4mA
Flame signal (Min)5.5mA
Flame signal (Max)20mA